DataNet Wireless Temperature Logger

DNL910A

 

The DNL910A is a wireless temperature logger featuring one internal temperature sensor measuring between -20 and 50 °C and four external 2-wire inputs each capable of measuring temperature, voltage, current, frequency, pulse as well as dry contact.

With high accuracy and resolution across all inputs, the DNL910A records all measured data to its internal memory before transmitting wirelessly over the DataNet network to the online DataSuite monitoring software.

The DNL910A's compact and robust casing is suitable for most industrial applications. This model includes a 2-row LCD screen and two-button keypad for standalone operation, such as joining the device to the wireless network, as well as a rechargeable battery pack for long-term deployment. Depending on the logger configuration, the DNL910 can run up to several months on one charge. External alarm output is available as well as 12 V excitation for powering external sensors.

DNL910A can also function as a Repeater, providing the logger with the ability to not only record and transmit its own data but also to relay transmissions from other units, thereby enhancing the DataNet's mesh network capabilities.


Key product benefits:

  • Up to 5 measurement inputs with high accuracy and resolution
  • Real-time, wireless transmission to PC with adjustable sampling and transmission rates to conserve battery power.
  • LCD for online viewing of data samples
  • Support for scalable units, when connecting external sensors based on current or voltage outputs
  • Four level alarm configuration with email/SMS notification and onboard alarm buzzer
  • Long-lasting rechargeable battery for standalone monitoring
  • 21 CFR Part 11 compliant

 

INPUT TYPES

 

4 to 20 mA

 

• Range: 4 to 20 mA
• Resolution: 47.6 μA
• Accuracy: ±0.5 %
• Loop impedance: 21 Ω

0 to 50 mV

• Range: 0 to 50 mV
• Resolution: 37 μV
• Accuracy: ±0.5 %
• Input impedance: 25 MΩ
• Maximum voltage: 3.2 V

0 to 1 V

• Range: 0 to 1 V
• Resolution: 200 μV
• Accuracy: ±0.5 %
• Input impedance: 25 MΩ
• Maximum voltage: 3.2 V

Temperature PT-100 (2-wires)

• Range: -200 to 400 ˚C
• Resolution: 0.1 ˚C
• Accuracy:
-200 to -60 ˚C: ±0.5 %
60 to 400 ˚C: ±0.5 %
-60 to 60 ˚C: ±0.3 ˚C

Temperature Thermocouple J

• Range: -200 to 1,000 ˚C
• Resolution: 0.1 ˚C
• Accuracy:
-200 to -60 ˚C: ±0.5 %
60 to 1,000 ˚C: ±0.5 %
-60 to 60 ˚C: ±0.5 ˚C
• Cold junction compensation error: ±0.3 ˚C

Temperature Thermocouple K

• Range: -200 to 1,000 ºC
• Resolution: 0.1 ˚C
• Accuracy:
-200 to -60 ˚C: ±0.5 %
60 to 1,000 ˚C: ±0.5 %
-60 to 60 ˚C: ±0.5 ˚C
• Cold junction compensation error: ±0.3 ˚C

Temperature Thermocouple T

• Range: -200 to 400 ˚C
• Resolution: 0.1 ˚C
• Accuracy:
-200 to -60 ˚C: ±0.5 %
60 to 400 ˚C: ±0.5 %
-60 to 60 ˚C: ±0.5 ˚C
• Cold junction compensation error: ±0.3 ˚C

Contact (for Switch/Door Position)

• Range: Open/Closed

Pulse Counter (input 4 only)

• Range: 1 to 65,536 counts
• Resolution: 1 count
• Frequency range: 0 to 4,000 Hz
• Input signal: 0 to 5 V
• Input impedance: 470 Ω

Frequency (input 4 only)

• Range: 20 Hz to 4 KHz
• Input signal: 0 to 5 V
• Input impedance: 470 Ω

Internal Temperature

• Range: -20 to 50 ˚C
• Resolution: 0.1 ˚C
• Accuracy: ±0.3 ˚C

OUTPUTS

External Power Excitation (transducers usage)

• 12 V DC @ 300 mA
• Reset fuse overload

Dry Contact Alarm Output

• Open collector
• Close position resistance: 50Ω
• Max. Load: 50 mA, 3 V DC

SAMPLING FEATURES

• Memory capacity: ~59,000 samples (depending on logger configuration)
• Sampling rate: Once every second to once every 18 hours
• Channel separation: 80 dB

RF NETWORK COMMUNICATION

• Frequency: 2.4 GHz
• Units per network: Up to 65,000
• Data rate: 250 Kbps
• Full mesh network architecture supported
• 128-bit network security encryption
• Worldwide license-free
• RF Transmission: 4 dbm

HARDWARE SPECIFICATIONS

Display/Keypad

• 2-row LCD with 16 character display
• 2-button keypad for standalone operation

Power Supply

• Internal rechargeable 4.8 V 800 mAh NiMH battery
• External 12 V DC input @ 300 mA 3.6 VA
• Battery Life: Up to 10 months, depending on logger configuration

Operating Temperature Range

-20 to 50 ˚C

Casing

• Plastic PC-ABS
• Dimensions: 9.7 x 9.3 x 2.7 cm
• Weight: 200 g
• Supports table and wall mounting

Standards Compliance

• CE, FCC, IC Canada
• Water and dust proof: IP54

 

12752
PT-100 Temperature Probe (2-wire), 4 m cable
12751
PT-100 Temperature Probe (2-wire), 6 m cable
50116
PT-100 Cryogenic Temperature Probe (2-wire), 2.5 m cable
12753
PT-100 Temperature Probe (2-wire), 2.5 m cable
DataSuite-DN
DataSuite Software for DataNet
DS-CFR-DN
DatPass CFR Admin Software for DataNet
50165
Thermocouple Type K Probe with Flat Pin Connector
11304
Rechargeable Battery Pack for DaqLink and DataNet Loggers
13825A
External Siren + Strobe Alarm
11506
Replacement Terminal Block for External Device Inputs
DT043
High Accuracy External Temperature and Humidity Probe
50129
Magnetic Door Contact Alarm Sensor
50114A
Weather Box - Small
AD001
12 VDC Universal Power Supply (EU, AUS, USA, UK)
Agriculture
Cold Chain
Food
Heavy Industry Productions
Hospital Health
Laboratories
Museums
Pharmaceutical
Schools Universities
Transportation
Warehouses Storage
DNL808A-BXT
Mini DataNet Wireless Temperature Logger with External Probe
DNL810A-BXT
Mini DataNet Wireless Temperature and Humidity Logger
DNL920A
DataNet Wireless Temperature and Humidity Logger
DNR900A
DataNet Receiver/Repeater
DBSA710A
DaqLink Temperature Logger